Loading product advisor...
Three-phase power is the backbone of industrial energy supply. With three phase-shifted alternating currents, it enables efficient operation of electric motors and high-performance systems. Our calculators consider the √3 factor for precise three-phase calculations.
Total power in three-phase systems
Effective power in three-phase motors
Reactive power in three-phase systems
Ratio of active to apparent power
Ratio of reactive to apparent power
Three-phase power consists of three alternating currents shifted by 120°. This enables constant power output and efficient energy transmission. The √3 factor (approx. 1.732) is characteristic of all three-phase calculations. Typical applications include electric motors, industrial plants, and high-voltage transmission with 400V voltage.
Calculate the apparent power, voltage or current.
S = U × I × √3
💡 Enter the known values – leave the field you want to calculate empty.
Example Calculation:
A 400 Volt three-phase motor has a rated current of 129.9 Ampere. What apparent power results from these values?
S = U × I × √3
S = 400 V × 129.9 A × √3
S = 90 kVA
Units of Measurement:
Apparent Power S = Kilovolt-Ampere [kVA]
Voltage U = Volt [V]
Current I = Ampere [A]
√3 or 1.73 = unitless
Calculate the active power, voltage, current or power factor.
P = U × I × cos φ × √3
💡 Enter the known values – leave the field you want to calculate empty.
Example Calculation:
A 400 Volt three-phase standard motor has a rated current of 25.18 Ampere and a cos φ of 0.86. What electrical power results from these values?
P = U × I × cos φ × √3
P = 400 V × 25.18 A × 0.86 × √3
P = 15.003 kW or 15 kW
Units of Measurement:
Active Power P = Kilowatt [kW]
Voltage U = Volt [V]
Current I = Ampere [A]
cos φ = unitless
√3 or 1.73 = unitless
Calculate the reactive power, voltage, current or sin φ.
Q = U × I × sin φ × √3
💡 Enter the known values – leave the field you want to calculate empty.
Example Calculation:
A 400 Volt three-phase standard motor has a rated current of 34.516 Ampere and a sin φ of 0.92. What reactive power results from these values?
Q = U × I × sin φ × √3
Q = 400 V × 34.516 A × 0.92 × √3
Q = 22 kVAr
Units of Measurement:
Reactive Power Q = Kilovolt-Ampere Reactive [kVAr]
Voltage U = Volt [V]
Current I = Ampere [A]
sin φ = unitless
√3 or 1.73 = unitless
Calculate cos φ, active power or apparent power.
cos φ = P / S
💡 Enter the known values – leave the field you want to calculate empty.
Example Calculation:
A 4.0 kW three-phase motor (or 400V electric motor) has a cos phi of 0.85. What apparent power results from these values?
cos φ = P / S
S = P / cos φ
S = 4.0 kW / 0.85
S = 4.706 kVA
Units of Measurement:
Active Power P = Kilowatt [kW]
Apparent Power S = Kilovolt-Ampere [kVA]
cos φ = unitless
Calculate sin φ, reactive power or apparent power.
sin φ = Q / S
💡 Enter the known values – leave the field you want to calculate empty.
Example Calculation:
A three-phase motor with apparent power of 15 kVA has a sin phi of 0.33. What reactive power results from these values?
sin φ = Q / S
Q = S × sin φ
Q = 15 kVA × 0.33
Q = 4.95 kVAr
Units of Measurement:
Reactive Power Q = Kilovolt-Ampere Reactive [kVAr]
Apparent Power S = Kilovolt-Ampere [kVA]
sin φ = unitless
U ist die Spannung in Volt, I der Strom in Ampere. Der Faktor √3 (rund 1,732) ist kennzeichnend für alle Drehstromberechnungen, weil Drehstrom aus drei um 120° phasenverschobenen Wechselströmen besteht.
Die Scheinleistung setzt sich aus Wirkleistung und Blindleistung zusammen. Anders als diese beiden ist sie unabhängig von der Phasenverschiebung φ. Bei gleicher Scheinleistung ist die Blindleistung umso größer, je größer der Winkel zwischen 0 und 90° ist.
Ein 400-V-Drehstrommotor hat einen Nennstrom von 129,9 A.
S = U × I × √3
S = 400 V × 129,9 A × √3
S = 90 kVA
Thanks for subscribing!
This email has been registered!